Checking Pressure Switch (Pressostat)
Checking Pressure Switch (Pressostat)
- Filling point low pressure side (blue hose) connected to service valve.
- Engine idling.
- Place blower fan switch to position 0.
- Place Air Conditioning (A/C) switch to off,
- Disconnect the pressure switch (Pressostat) connector,
Start the compressor by connecting the magnetic clutch cable to the battery positive terminal.
WARNING
The compressor may be connected like this for a maximum of 3 minutes.
Connect an ohmmeter over both pressure switch (Pressostat) terminals.
NOTE: If the pressure falls below 140 kPa, but the ohmmeter continues to display 0 [ohm], stop and disconnect the compressor.
The ohmmeter should read infinite resistance at a compressor pressure of 150 - 170 kPa.
OK - Test Complete
Not OK - Refer to Replacing the Component.