Instrument Panel Vents Spraying Water
A/C Refrigerant System Troubleshooting
Instrument Panel Vents Spraying Water
- Check evaporator drain pipe for proper routing (should not be kinked or pinched).
- Check evaporator water drain valve.
• Must not be plugged with wax, dirt or undercoating (clean if necessary)
• Valve door must open/close properly
- Check plenum tray.
• Must be properly installed and not damaged