Conditions
B1345
Mixed-air sensor LH. Short to ground
Mixed-air sensor LH. Open circuit/short to B+
Fault symptoms
Perceived temperature in cabin too high or too low compared to the set temperature.
Conditions
The following conditions apply:
- Open circuit or short to B+ on pin 19 >4.9 V.
- Short to ground on pin 19<0.1 V.
- Measured every 440 ms and 5 consecutive measurements are required to set a diagnostic trouble code.
- The diagnostic trouble code is deleted after the ignition has been switched on 20 times if the fault conditions have not been fulfilled.
- When the diagnostic trouble code is set, the control module uses the default value, which is the relative opening of the air-mixing flap in question multiplied by the coolant temperature.