Charging Refrigerant System (Liquid)
NOTE: This step is to charge an empty system through the high pressure side with refrigerant in a liquid state. When the refrigerant container is held upside down, refrigerant will enter the system as a liquid.
CAUTION: Never run the engine when charging the system through the high pressure side. Do not open the low pressure valve when the system is being charged with liquid refrigerant.
1. Close both high and low pressure valves completely after the system is evacuated.
2. Install the refrigerant can tap valve as described in "Handling Refrigerant Service Tap Valve" section.
3. Open the high pressure valve fully, and keep the container upside down.
4. Charge the system to the specified amount by weighing the refrigerant with a scale. Overcharging will cause discharge pressure (high side) to rise. Then, close the high pressure valve.
Specified amount: 670 ± 25 g (1.49 ± 0.6 lb)
NOTE: If the low pressure gauge does not show a reading, the system is restricted and must be repaired.
5. After the specified amount of refrigerant has been charged into system, close the manifold gauge valve.
6. Confirm that there are no leaks in the system by checking with a leak detector. Refer to Checking Refrigerant Leak.
NOTE: Conducting a performance test prior to removing the manifold gauge is good service operation.