Excessive Refrigerant or Insufficient Condenser Cooling
Measured pressureLow-pressure side: 34.1 psi
(235 kPa, 2.40 kg/Sq.cm)
High-pressure side: 327 psi
(2,256 kPa, 23.0 kg/Sq.cm)
Condition
Insufficient cooling.
NOTE: If condenser fan does not operate when air conditioner is operating, refer to "Condenser Fan Does Not Operate" before proceeding.
Step 1
1. Check condenser for bent fins or damage.
2. If condenser is OK, discharge excess refrigerant. Refer to operating instructions of your refrigerant recovery/recycling/charging station for proper procedures.
CAUTION: Always wear gloves and eye protection when discharging refrigerant.
3. Verify that refrigerant pressure is normal.