Manufacturer Code Charts
Control Panel Fault Code Diagnosis
Condition(s):
NOTE: Reference fault code #23*: In ambient temperatures below 0°C, this code may be logged because the low ambient causes a temporary low gas pressure.
NOTE: Where the ambient temperature rises above 40°C, with the engine close to overheating, electrical feed to the compressor clutch may be cut and code #23 registered.
0 Normal operation no fault codes present
Possible Source(s):
- None
Action(s) to take:
- Wait 30 seconds for system self-check.
11 Motorized in-car aspirator malfunction
Possible Source(s):
- Harness / connector fault
- Sensor open / short circuit
Action(s) to take:
- Panel fault codes are not stored for motorized in-car aspirator motor failure.
12 Ambient temperature sensor malfunction
Possible Source(s):
- Harness / connector fault
- Sensor open / short circuit
Action(s) to take:
- After rectification, disconnect the vehicle battery for 10 seconds to reset the system.
13 Evaporator temperature sensor malfunction
Possible Source(s):
- Harness / connector fault
- Sensor open/short circuit
Action(s) to take:
- Refer to PDU
14 Water temperature input malfunction
Possible Source(s):
- Instrument cluster output
Action(s) to take:
- Refer to PDU
15 Heater matrix temperature sensor malfunction
Possible Source(s):
- Harness / connector fault
- Sensor open / short circuit
Action(s) to take:
- Refer to PDU
21 Solar sensor
Possible Source(s):
- Sensor open / short circuit
Action(s) to take:
- Refer to PDU
22 Compressor lock signal fault
Possible Source(s):
- Low refrigerant charge, low compressor oil level, loose drive belt
- Harness / connector fault
Action(s) to take:
- Adjust items as required
23 Refrigerant pressure switch malfunction
Possible Source(s):
- Harness / connector fault
- Switch open / short circuit
Action(s) to take:
- Refer to PDU
23 Refrigerant pressure low refrigerant charge*
Possible Source(s):
- Leak from damaged pipe or joint
Action(s) to take:
- Rectify as required & recharge system
24 Face vent demand potentiometer fault
Possible Source(s):
- Potentiometer open / short circuit
- Harness / connector fault
Action(s) to take:
- Refer to PDU
31 LH fresh / recirc. potentiometer fault
Possible Source(s):
- Harness / connector fault
- In certain circumstances the servo motor may over-travel & cause further logged faults. This may be cured, following fault rectification, by cycling the ignition ON-OFF-ON 3 times
Action(s) to take:
- Refer to PDU
32 RH fresh / recirc. potentiometer fault
Possible Source(s):
- Harness / connector fault
- In certain circumstances the servo motor may over-travel & cause further logged faults. This may be cured, following fault rectification, by cycling the ignition ON-OFF-ON 3 times
Action(s) to take:
- Refer to PDU
33 Cool air by-pass potentiometer fault
Possible Source(s):
- Harness / connector fault
- In certain circumstances the servo motor may over-travel & cause further logged faults. This may be cured, following fault rectification, by cycling the ignition ON-OFF-ON 3 times
Action(s) to take:
- Refer to PDU
34 Defrost vent potentiometer fault
Possible Source(s):
- Harness / connector fault
- In certain circumstances the servo motor may over-travel & cause further logged faults. This may be cured, following fault rectification, by cycling the ignition ON-OFF-ON 3 times
Action(s) to take:
- Refer to PDU
35 center vent potentiometer fault
Possible Source(s):
- Harness / connector fault
- In certain circumstances the servo motor may over-travel & cause further logged faults. This may be cured, following fault rectification, by cycling the ignition ON-OFF-ON 3 times
Action(s) to take:
- Refer to PDU
36 Foot vent potentiometer fault
Possible Source(s):
- Harness / connector fault
- In certain circumstances the servo motor may over-travel & cause further logged faults. This may be cured, following fault rectification, by cycling the ignition ON-OFF-ON 3 times
Action(s) to take:
- Refer to PDU
41 LH fresh 1 recirc. motor fault
Possible Source(s):
- Harness / connector fault
- Servo motor seized or sticking
- Flap seized or sticking
Action(s) to take:
- Refer to PDU
42 RH fresh / recirc. motor fault
Possible Source(s):
- Harness / connector fault
- Servo motor seized or sticking
- Flap seized or sticking
Action(s) to take:
- Refer to PDU
43 Cool air by-pass motor fault
Possible Source(s):
- Harness / connector fault
- Servo motor seized or sticking
- Flap seized or sticking
Action(s) to take:
- Refer to PDU
43 Cool Air by-pass motor fault
Possible Source(s):
- Harness / connector fault
- Servo motor seized or sticking
- Flap seized or sticking
Action(s) to take:
- Refer to PDU
44 Defrost vent motor fault
Possible Source(s):
- Harness / connector fault
- Servo motor seized or sticking
- Flap seized or sticking
Action(s) to take:
- Refer to PDU
45 center vent motor fault
Possible Source(s):
- Harness / connector fault
- Servo motor seized or sticking
- Flap seized or sticking
Action(s) to take:
- Refer to PDU
46 Foot vent motor fault
Possible Source(s):
- Harness / connector fault
- Servo motor seized or sticking
- Flap seized or sticking
Action(s) to take:
- Refer to PDU